Code Name YJLHV22
0.6/1KV
Number of conductors:1,2,3,4,5
Maximum conductor temperature in normal use: 90℃
| BASIC INFORMATION | |
| Code Name | YJLHV22 |
| Rated Voltage (Uo/U) | 0.6/1KV |
| Cable Structure | Aluminum Alloy Conductor/XLPE Insulation/PVC Inner Sheath/Steel Tape Armoured/PVC Outer Sheath |
| CONSTRUCTION | |
| Conductor | Number of conductors:1,2,3,4,5 |
| Insulation | XLPE(Cross-linked Polyethylene) according to IEC |
| Sheath | PVC(Polyvinyl Chloride) according to IEC |
| CHARACTERISTICS | |
| Conductor Temperature | Maximum conductor temperature in normal use: 90℃ |
| Max.short-circuit Temperature | Maximum shall not exceed 250℃(5s Max,Duration) |
| Installation Temperature | Ambient temperature under installation shall not be below 0℃ |
| Minimum Bending Radius | The bending radius of cable: (D-Diameter of cable) |
| Nominal Cross Sectional Area(mm²) | No.of Cores | Nominal Insulation Thickness(mm) | Approx Overall Diameter(mm) | Cable Weight Max(kg/km) |
|---|---|---|---|---|
| 4 | 1 | 0.7 | 6.4 | 58 |
| 6 | 1 | 0.7 | 7 | 69 |
| 10 | 1 | 0.7 | 8.3 | 94 |
| 16 | 1 | 0.7 | 9.3 | 121 |
| 25 | 1 | 0.9 | 11.2 | 175 |
| 35 | 1 | 0.9 | 12.4 | 215 |
| 50* | 1 | 1 | 14.1 | 278 |
| 70* | 1 | 1.1 | 16.1 | 362 |
| 95* | 1 | 1.1 | 18.2 | 468 |
| 120* | 1 | 1.2 | 18.7 | 539 |
| 150* | 1 | 1.4 | 20.7 | 658 |
| 185* | 1 | 1.6 | 22.6 | 763 |
| 240* | 1 | 1.7 | 25.1 | 952 |
| 300* | 1 | 1.8 | 27.5 | 1172 |
| 400* | 1 | 2 | 30.9 | 1478 |
| 500* | 1 | 2.2 | 34.5 | 1861 |
| 630* | 1 | 2.4 | 38.5 | 2299 |
| 800* | 1 | 2.8 | 46 | 2937 |
| 4 | 2 | 0.7 | 11.7 | 115 |
| 6 | 2 | 0.7 | 12.7 | 139 |
| 10 | 2 | 0.7 | 15.3 | 195 |
| 16 | 2 | 0.7 | 17.4 | 257 |
| 25 | 2 | 0.9 | 20.8 | 269 |
| 35 | 2 | 0.9 | 23.1 | 460 |
| 50* | 2 | 1 | 19.6 | 478 |
| 70* | 2 | 1.1 | 22.6 | 646 |
| 95* | 2 | 1.1 | 25.8 | 849 |
| 120* | 2 | 1.2 | 28.2 | 1042 |
| 150* | 2 | 1.4 | 40.2 | 1520 |
| 185* | 2 | 1.6 | 44.2 | 1800 |
| 240* | 2 | 1.7 | 49.6 | 2329 |
| 300* | 2 | 1.8 | 54.8 | 3076 |
| 4 | 3 | 0.7 | 12.2 | 135 |
| 6 | 3 | 0.7 | 13.4 | 167 |
| 10 | 3 | 0.7 | 16.1 | 238 |
| 16 | 3 | 0.7 | 18.4 | 318 |
| 25 | 3 | 0.9 | 22.1 | 463 |
| 35 | 3 | 0.9 | 24.6 | 584 |
| 50* | 3 | 1 | 23.7 | 677 |
| 70* | 3 | 1.1 | 27.9 | 929 |
| 95* | 3 | 1.1 | 31.3 | 1212 |
| 120* | 3 | 1.2 | 38.4 | 1593 |
| 150* | 3 | 1.4 | 43.1 | 2010 |
| 185* | 3 | 1.6 | 47.4 | 2384 |
| 240* | 3 | 1.7 | 53.2 | 3045 |
| 300* | 3 | 1.8 | 58.7 | 3810 |
| 400* | 3 | 2 | 66.5 | 4885 |
| 4 | 4 | 0.7 | 13.2 | 162 |
| 6 | 4 | 0.7 | 14.5 | 201 |
| 10 | 4 | 0.7 | 17.6 | 290 |
| 16 | 4 | 0.7 | 20.1 | 392 |
| 25 | 4 | 0.9 | 24.3 | 577 |
| 35 | 4 | 0.9 | 27.1 | 731 |
| 50* | 4 | 1 | 26.2 | 884 |
| 70* | 4 | 1.1 | 31.9 | 1236 |
| 95* | 4 | 1.1 | 35.9 | 1595 |
| 120* | 4 | 1.2 | 42.8 | 2064 |
| 150* | 4 | 1.4 | 47.9 | 2579 |
| 185* | 4 | 1.6 | 52.9 | 3085 |
| 240* | 4 | 1.7 | 59.3 | 3939 |
| 300* | 4 | 1.8 | 65.5 | 4929 |
| 400* | 4 | 2 | 74.4 | 6351 |
| 4 | 5 | 0.7 | 14.2 | 190 |
| 6 | 5 | 0.7 | 15.6 | 237 |
| 10 | 5 | 0.7 | 19.1 | 346 |
| 16 | 5 | 0.7 | 22 | 470 |
| 25 | 5 | 0.9 | 26.6 | 697 |
| 35 | 5 | 0.9 | 29.7 | 887 |
| 50* | 5 | 1 | 32.6 | 1132 |
| 70* | 5 | 1.1 | 37.8 | 1536 |
| 95* | 5 | 1.1 | 42.8 | 2053 |
| 120* | 5 | 1.2 | 47.3 | 2541 |
| 150* | 5 | 1.4 | 53.1 | 3201 |
| 185* | 5 | 1.6 | 58.6 | 3692 |
| 240* | 5 | 1.7 | 65.8 | 4882 |
| 300* | 5 | 1.8 | 72.7 | 6108 |
| 400* | 5 | 2 | 82.7 | 7899 |

.jpg)
Related Products
More +
Conductor:Flat grain annealed copper, multi - stranded in line with IEC(EN) 60228 class 2.
Insulation:Crosslinked polyethylene complex
Sheath:LSZH compounds

Fire resistant:EC60331;B56387;SS 299
Flame retardant : IEC 60332; BS4066;BS EN 50266;IEEE 383
Smoke emission:IEC61034;BS 7622;BSEN 50268

Fire resistant:EC60331;B56387;SS 299
Flame retardant : IEC 60332; BS4066;BS EN 50266;IEEE 383
Smoke emission:IEC61034;BS 7622;BSEN 50268

conductor:Flat grain annealed copper, multi - stranded in line with IEC(EN) 60228 class 2.
insulation:Crosslinked polyethylene complex
armoured:Double steel belt